BACnet Interface - Multi-State Output Object - Command Control of Lamp, Group and Channel
Multi-State Output Object - Command Control of Lamp, Group and Channel
To control DALI scenes and other commands for the lamps, groups and channels, use Multi-State Output objects. Among other things recall, store and delete scenes with these objects.
Lamp, Group and Channel
List of available properties for these objects.
| Property Identifier | Property ID | Property Datatype | Conformance Code |
|---|---|---|---|
| Object_Identifier | 75 | BACnetObjectIdentifier | R |
| Object_Name | 77 | CharacterString | R |
| Object_Type | 79 | BACnetObjectType | R |
| Present_Value | 85 | Unsigned | W |
| Status_Flags | 111 | BACnetStatusFlags | R |
| Event_State | 36 | BACnetEventState | R |
| Reliability | 103 | BACnetReliability | R |
| Out_Of_Service | 81 | BOOLEAN | W |
| Number_Of_States | 74 | Unsigned | R |
| State_Text | 110 | BACnetARRAY[N]of CharacterString | R |
| Priority_Array | 87 | BACnetPriorityArray | R |
| Relinquish_Default | 104 | REAL | R |
Object_Identifier
The object instance number is the same as the associated Analog Output object and is also represented as TCLL.
-
"T" is the type of object as follows, 0 for DALI lamps, 1 for DALI groups and 2 for DALI channels.
-
"C" represents the DALI channel number, 0, 1, 2, or 3.
-
"LL" represents for group objects, numbers 0-15 and for channel objects, number 00.
Object_Name
The Object_Name of the associated Analog Output object of the Group or Channel ending with "Scene".
Object_Type
MULTISTATE_OUTPUT (14).
Present_Value
Among other things the Present_Value allows recalling, storing, and deleting the scenes. The available values are described below.
GO TO SCENE (1-16)
Allow sending the DALI command "GO TO SCENE" to the associated lamp, group or channel (broadcast).
STORE SCENE (17-32)
Allow sending the DALI command "STORE DTR AS SCENE" to the associated lamp, group or channel (broadcast).
REMOVE SCENE (33-48)
Allow sending the DALI command "REMOVE FROM SCENE" to the associated lamp, group or channel (broadcast).
NO COMMAND (50)
No command is executed.
RESET RUN HOURS (53)
Reset the run hours to zero.
EMERGENCY FUNCTION TEST START (55)
Start the function test for the lamps of the type "Self-contained emergency lighting (device type 1)".
EMERGENCY DURATION TEST START (56)
Start the duration test for the lamps of the type "Self-contained emergency lighting (device type 1)".
EMERGENCY TESTS STOP (57)
Stop the current test for the lamps of the type "Self-contained emergency lighting (device type 1)".
DIM UP (58)
Allow sending the DALI command "UP" to the associated lamp, group or channel (broadcast).
DIM ON AND UP (59)
Allow sending the DALI command "ON AND STEP UP" to the associated lamp, group or channel (broadcast).
DIM DOWN (60)
Allow sending the DALI command "DOWN" to the associated lamp, group or channel (broadcast).
DIM DOWN AND OFF (61)
Allow sending the DALI command "STEP DOWN AND OFF" to the associated lamp, group or channel (broadcast).
OFF (65)
Allow sending the DALI command "OFF" to the associated lamp, group or channel (broadcast).
DIM STEP UP (66)
Allow sending the DALI command "STEP UP" to the associated lamp, group or channel (broadcast).
DIM STEP DOWN (67)
Allow sending the DALI command "STEP DOWN" to the associated lamp, group or channel (broadcast).
RECALL MIN LEVEL (68)
Allow sending the DALI command "RECALL MIN LEVEL" to the associated lamp, group or channel (broadcast).
RECALL MAX LEVEL (69)
Allow sending the DALI command "RECALL MAX LEVEL" to the associated lamp, group or channel (broadcast).
RECALL LAST LEVEL (70)
Recall Last Level.
EMERGENCY REST (71)
For the "Self-contained emergency lighting (device type 1)" only, starts the rest mode.
In this mode the lamp is intentionally off when it is powered from the battery.
Refer to the specification IEC 62386-202 for the complete details on the rest mode.
EMERGENCY INHIBIT (72)
For the "Self-contained emergency lighting (device type 1)" only, starts the inhibit mode.
In this mode the lamp is powered from the mains power supply but it is also prevented for 15 minutes from going into the emergency mode when an event of mains power failure occurs.
Refer to the specification IEC 62386-202 for the complete details on the inhibit mode.
EMERGENCY RESET INHIBIT (73)
For the "Self-contained emergency lighting (device type 1)" only, cancels the inhibit timer.
Refer to the specification IEC 62386-202 for the complete details on the inhibit mode.
EMERGENCY RESET FUNCTION TEST DONE FLAG (74)
For the "Self-contained emergency lighting (device type 1)" only, resets the function test done flag.
Refer to the specification IEC 62386-202 for the complete details on this command.
EMERGENCY RESET DURATION TEST DONE FLAG (75)
For the "Self-contained emergency lighting (device type 1)" only, resets the duration test done flag.
Refer to the specification IEC 62386-202 for the complete details on this command.
EMERGENCY START IDENTIFICATION (76)
For the "Self-contained emergency lighting (device type 1)" only, starts the identification.
Refer to the specification IEC 62386-202 for the complete details on this command.
GROUP ADD (77-92)
Allow sending the DALI command "ADD TO GROUP" to the associated lamp, group or channel (broadcast).
GROUP REMOVE (93-108)
Allow sending the DALI command "REMOVE FROM GROUP" to the associated lamp, group or channel (broadcast).
Status_Flags
This property indicates the general "reliability" of the object.
Reliability
This property indicates whether the operation of the Present_Value or the operation of the object is reliable. The values are as follows:
- NO_FAULT_DETECTED (0) - No fault has been detected.
Out_Of_Service
It is an indication of whether or not the object is in service.